JUMO AQUIS 500 pH – pH, ORP and ammonia measuring transducer and controller

Process analyzers and sensors, Water analysis

Fields of application

JUMO AQUIS 500 pH is a universal measuring transducer and controller for monitoring pH, oxidation-reduction potential (ORP), ammonia concentration and temperature. It is used in drinking water, wastewater treatment, industrial processes and refrigeration systems. The modular design allows you to select the required analog and relay outputs.

 

Features:

  • pH, ORP, ammonia (NH₃) and temperature measurements
  • Automatic temperature compensation
  • Graphic LCD display with backlight
  • P, PI, PD and PID control functions
  • Up to 2 analog outputs and 2 relays
  • Integrated calibration and electrode diagnostics functions
  • Compatible with Pt100, Pt1000 and ISFET sensors
  • IP67 protection class for wall-mounted version
  • Panel or wall mountingEasy parameter setting and multilingual menu
  • SPECIFICATIONS
  • AVAILABLE MODELS
  • DOCUMENTS

SPECIFICATIONS

  • Device type

    Measuring transducer and regulator
  • Measured parameters

    pH, ORP, NH₃, temperature
  • pH measuring range

    –1 to +15 pH
  • ORP measurement range

    –1500 to +1500 mV
  • Ammonia measurement range

    0-9999ppm
  • Temperature measurement range

    -50 to +250 °C (Pt100/Pt1000)
  • Measurement accuracy

    ≤0.3 % (pH, ORP, NH₃)
  • Temperature measurement accuracy

    ≤0.5°C (Pt100/Pt1000)
  • Analog inputs

    2 (main measurement and temperature)
  • Digital inputs

    1
  • Analog outputs

    Up to 2 (0/4-20mA or 0-10V)
  • Relay outputs

    Up to 2 (switchable)
  • Regulation functions

    P, PI, PD, PID
  • Display

    Graphic LCD with backlight
  • Power supply

    110-240V AC, 20-30V AC/DC or 12-24V DC
  • Energy consumption

    About 14 VA
  • Ambient temperature

    –15 to +65°C
  • Security class

    IP67 (wall), IP65 front (panel)
  • Housing material

    ABS plastic
  • Assembly

    On the wall or control panel
  • Additional functions

    Calibration log, electrode diagnostics, temperature compensation

AVAILABLE MODELS

DOCUMENTS

  • Brochure: Liquid Analysis

    10.32 MB

    Download
  • Brochure: Application: Cleaning in Place (CIP)

    4.35MB

    Download
  • Brochure: Product range – (overview in DIN A4 format)

    5.62 MB

    Download
  • Brochure: Chemical Industry

    7.93 MB

    Download
  • Brochure: Meat Processing Industry

    13.6 MB

    Download
  • Brochure: pH measurement in a flue gas desulfurization unit (FGD)

    686.03 KB

    Download
  • Brochure: Water and Wastewater

    9.87 MB

    Download
  • Brochure: Product range

    9.72 MB

    Download
  • Product Checklist: pH / ORP (Redox)

    337.1 KB

    Download
  • Operating instructions: JUMO AQUIS 500 pH – pH, redox, voltage and NH3 (ammonia) concentration converter/controller

    1.34 MB

    Download
  • Data sheet: JUMO AQUIS 500 pH

    534.68 KB

    Download
  • Certificate: UL 61010-1 – JUMO AQUIS 500 series, type 202560, 202565, 202566, 202568, 202569

    158.62 KB

    Download
  • Certificate: China RoHS-20 – JUMO AQUIS 500 pH

    98.5 KB

    Download
  • Order information: 202560

    131.78 KB

    Download
  • EU Declaration of Conformity: JUMO AQUIS 500 pH

    167.38 KB

    Download