BENNING INVERTRONIC modular – three-phase modular inverter system

DC/AC inverters

Fields of application

Uninterruptible three-phase power supply for critical loads in information technology, telecommunications and industry, where high reliability and power expansion without system shutdown are required.

 

Features:

  • Three-phase modular system: modules 10 kVA (48 V DC) and 15 kVA (110 / 220 V DC)
  • Up to 90 kVA in one cabinet, up to 12 modules when connecting two cabinets
  • N+1 redundancy, each module with its own static bypass
  • Hot swapping and power swapping without powering down the load
  • Efficiency not less than 92 %, ≥ 90 % and at a load of 50 %
  • Less weight and footprint than conventional single-unit systems
  • SPECIFICATIONS
  • AVAILABLE MODELS
  • DOCUMENTS

SPECIFICATIONS

  • Manufacturer

    BENNING
  • Series

    INVERTRONIC modular
  • Device type

    Three-phase modular inverter system with hot-swappable modules, powered by a central battery
  • Input DC voltage

    48 V, 110 V or 220 V (range –15 % to +20 %)
  • Output voltage

    400 / 230 V, three-phase; 50 (60) Hz
  • Module power

    10 kVA (48 V DC) or 15 kVA (110 / 220 V DC)
  • System power

    Up to 50 kVA (48 V) or up to 90 kVA (110 / 220 V) in one cabinet; higher by connecting two cabinets (up to 12 modules)
  • Reservation

    N+1; the system supplies 100 % power even if one module fails
  • Static bypass

    In each inverter module; the load is returned to the inverter without interruption
  • Output power according to power factor

    100 % power, when the load leading cos φ is not more than 0.8
  • Overload

    150 % 60 s; 125 % 10 min
  • Utility

    Not less than 92 % (110 / 220 V DC); not less than 89 % (48 V DC); ≥ 90 % at 50 % load (110 / 220 V)
  • Environment

    0 to +40 °C; storage –25 to +70 °C; humidity 5–95 % non-condensing; altitude up to 1000 m without derating; noise approx. 65 dB(A)
  • Security class

    IP20
  • Standards

    EMC IEC 62040 C3; EN 50091-1-1
  • Interfaces

    RS 232 or RS 485 (Modbus); 6 dry relay contacts; optional Profibus and network adapter