en
  • lt
  • en

BENNING INVERTRONIC – single-phase and three-phase IGBT inverter for industry, 10–200 kVA

DC power supply, DC/AC inverters

Fields of application

AC power supply for process-critical consumers, independent of public grid disruptions: power plants, oil, gas and petrochemicals, processing industry.

 

Features:

  • Single-phase and three-phase IGBT inverter with sinusoidal output voltage and isolation transformer
  • High output quality: voltage tolerance ±1 %, THDu up to 1 %
  • Parallel operation of up to 8 systems with active load balancing
  • Connecting A and B buses without switching to bypass
  • Uses existing battery and rectifier infrastructure, batteries 110 or 220 V
  • Digital control, MCU 3000, Modbus, Profibus, SNMP and other protocols
  • SPECIFICATIONS
  • AVAILABLE MODELS
  • DOCUMENTS

SPECIFICATIONS

  • Manufacturer

    BENNING
  • Series

    INVERTRONIC
  • Device type

    Single-phase and three-phase IGBT inverter (DC/AC) with digital control, isolation transformer and bypass line
  • Power range

    Three-phase: 10–200 kVA; single-phase: 10–120 kVA (cosφ 0.8; at cosφ 1.0 – exactly the same kW)
  • Output voltage

    Three-phase: 380 / 400 / 415 V; single-phase: 220 / 230 / 240 V (others on request)
  • Battery voltage

    110 V or 220 V (higher on request)
  • Output quality

    Sinusoidal voltage; static tolerance ±1 %; frequency tolerance ±0.1 %; THDu up to 1 % (linear load)
  • Utility

    Three-phase: up to 95 %; single-phase: up to 93 % (depending on configuration)
  • Overload (inverter)

    200 % 1 s; 150 % 60 s; 125 % 10 min
  • Overload (bypass)

    Three-phase: 1000 % 100 ms, 150 % 10 min; single-phase: 500 % 100 ms, 150 % 10 min
  • Short-circuit current (inverter)

    Three-phase: up to 350 % 1 s; single-phase: up to 300 % 1 s (higher on request; optional 7 × nominal)
  • Parallel work

    Up to 8 separate systems with active load sharing; connection of A and B buses without switching to bypass
  • Cooling

    Reserved forced ventilation
  • Working conditions

    0…40 °C (power is reduced at higher temperatures); humidity 5–95 % without condensation; altitude up to 1000 m
  • Security class

    IP20 (others on request); RAL 7035; cables from below (from above on request)
  • Noise

    Less than 65 dB(A) (depending on power)
  • Standards

    Safety IEC/EN 62040-1, IEC/EN 62477-1; EMC IEC/EN 62040-2; Performance IEC/EN 62040-3
  • Management and monitoring

    MCU 3000 with 10 inch touch screen; DNP 3, Profibus, Modbus, TCP/IP, SNMP, e-mail, modem, Ethernet, USB; RS-232, RS-485

AVAILABLE MODELS

DOCUMENTS