en
  • lt
  • en

BENNING rectifiers for nuclear power plants – rectifier for stationary battery systems (KTA)

AC/DC rectifiers, DC power supply

Fields of application

Protected DC power supply for critical loads in nuclear power plants, both during grid and power outage: power plant equipment, signaling, control and protection electronics, telemetry, communication equipment, static inverters, motors and solenoid valves.

 

Features:

  • Operates on lead-acid or NiCd batteries; output voltages 24, 110 and 220 V
  • Manufactured according to KTA guidelines, suitable for any type of power plant
  • Controlled 6-pulse thyristor bridge, IU characteristic according to DIN 41773
  • Stability: voltage ±1 %, current ±2 %
  • Comprehensive monitoring and centralized fault signaling available on MCU 2000
  • Optional test equipment for repetitive measurements
  • In case of seismic requirements, the cabinets are additionally reinforced
  • SPECIFICATIONS
  • AVAILABLE MODELS
  • DOCUMENTS

SPECIFICATIONS

  • Manufacturer

    BENNING
  • Series

    Rectifiers for nuclear power plants
  • Device type

    Thyristor rectifier for stationary battery systems in nuclear power plants; manufactured according to KTA guidelines
  • Output voltage

    24, 110 and 220 V
  • Current range

    24 V: 400-3000 A; 110V: 200-1600A; 220 V: 100-1200 A
  • Input

    3 × 400 V, 50 Hz with neutral wire (other voltages on request)
  • Regulation

    Controlled three-phase 6-pulse bridge with thyristors; ultra-fast fuses for semiconductors
  • Charging characteristic

    IU according to DIN 41773; lead: float 2.23 V/cell, fast 2.4 V/cell, starting up to 2.7 V/cell (W characteristic); NiCd: 1.4 / 1.55 V/cell, starting up to 1.8 V/cell.
  • Stability

    Voltage ±1 %; current ±2 %
  • Permissible deviations

    Mains voltage ±10 %; frequency ±5 %; load 0–100 %
  • Pulsations

    About 5 % (peak to peak) without battery, at 0-100 % load
  • Monitoring and alarm

    Mains, fuse, overvoltage, ripple and short circuit monitoring; centralised fault signalling SME I; optional MCU 2000 with event memory
  • Cooling

    Natural air (air enters from below)
  • Security class

    IP20; color RAL 7035
  • Ambient temperature

    –5…+40 °C; humidity class F according to DIN 40040
  • Standards

    EMC EN 50081-2, EN 50082-2
  • Additional equipment

    Battery switchboards BES 250–3200 A; test equipment for repetitive measurements

AVAILABLE MODELS

DOCUMENTS

  • Brochure: Rectifier Nuclear Power Plant

    447.89 KB

    Download