Manufacturer
Active Power (Piller Group)
Series
CLEANSOURCE® PLUS SMS
Device type
Flywheel UPS without batteries, single module, parallel online architecture
Rated power
300kW / 333kVA
Input voltage
380 / 400 / 415 V AC, 3 phases, 4 wires + ground
Input voltage range
+10 % / –15 % (400/415 V), ±10 % (380 V), programmable
Frequency
50/60 Hz ±10 % max (programmable), ±3 % default
Input power factor
0.99 at nominal load
Input current harmonics
< 2 % (linear load), < 8 % (non-linear), at 100 % load
Rated input current
472 A (380 V), 449 A (400 V), 432 A (415 V)
Output voltage
380 / 400 / 415 V AC; ±1 % in constant mode; ±1 % in 50 ms with 100 % load step
Output voltage distortion
< 1 % (linear), < 5 % (100 % non-linear load)
Load power factor
0.7 lagging / 0.9 ahead without power reduction
Overload (in network mode)
105 % continuous; < 110 % 10 min; < 125 % 5 min; < 150 % 1 min; < 200 % 10 s
Efficiency (storage tank connected)
93.6 % (25 %), 96.2 % (50 %), 96.7 % (75 %), 97.6 % (100 % load)
Energy storage
Integrated steel flywheel, 10,000 rpm, 6.2 MJ
Flywheel autonomy
20 s (100 %), 27 s (75 %), 39 s (50 %), 73 s (25 % load)
Flywheel charging time
< 3 min (nominal) at 65 kW
Parallel connection
Up to 8 systems
Bypass
Internal static bypass included; internal maintenance bypass optional
Input
Single or double (optional)
Short circuit resistance
65kA
Control
10" color touch screen; 8 programmable inputs and 8 outputs
Noise
< 75 dBA at 1 m distance
Operating temperature/storage
0–40°C / –25…+70°C
Humidity
5–95 % (without condensate)
Working height
Up to 914 m; every 304.8 m above – 1.2 °C derating
Heat dissipation
7.4 kW
Dimensions (W × D × H)
1488 × 865 × 1981mm
Weight
2177 kg
Cable entry
From above or below
Standards
EN 62040-1, EN 62040-2, EN 62040-3
Service
Annual inspection; flywheel bearing replacement every 4 years
Additional equipment available
dual entry, internal maintenance bypass, GenSTART™ generator start, remote monitoring, seismic package.