en
  • lt
  • en

JUMO 402006 multi-range differential pressure transmitter

Compact pressure transmitters, Pressure sensors

Fields of application

The JUMO 402006 is a multi-range differential pressure transmitter for measuring the differential pressure of non-aggressive gases. Adjustable measuring ranges, selectable current or voltage output signals and zero correction allow one device to be adapted to different ventilation, air conditioning, filter control and clean room systems.

Features:

  • Differential pressure measurement up to 100 hPa
  • 8 configurable measurement ranges in each main range group
  • Piezoresistive silicon sensor
  • Output 0(4)–20 mA or 0(2)–10 V
  • Adjustable signal attenuation
  • Zero point correction
  • Optional LCD display
  • Simple parameter setting via DIP switches
  • SPECIFICATIONS
  • AVAILABLE MODELS
  • DOCUMENTS

SPECIFICATIONS

  • Type

    Multi-range pressure and differential pressure transmitter
  • Type number

    402006
  • Measured pressure

    Differential relative pressure
  • Measuring principle

    Piezoresistive silicon sensor
  • Selection of measuring ranges

    The selected model has several ranges settable by DIP switches
  • 2.5-10 hPa version

    0…2.5 / 0…5 / 0…7.5 / 0…10 hPa or corresponding ± ranges
  • 25-100 hPa version

    0…25 / 0…50 / 0…75 / 0…100 hPa or corresponding ± ranges
  • Configurable ranges

    2.5 / 5 / 7.5 / 10 hPa or 25 / 50 / 75 / 100 hPa; bidirectional ± range also available
  • Measured medium

    Dry, non-aggressive gases
  • Medium temperature

    0…+60 °C
  • Accuracy

    1 % from the end value of the main measuring range
  • Long-term stability

    < ±0.1 % main range end value per year
  • Output signal

    0-20 mA or 4-20 mA, 3-wire; 0-10 V DC or 2-10 V DC, 3-wire
  • Output signal selection

    Configurable via DIP switch
  • Power supply

    15-38V DC or 12-28V AC
  • Process connection

    Hose connector Ø 6.6 × 10 mm for Ø 6 mm flexible hose
  • Electrical connection

    5-pole spring terminals, conductor cross-section up to 2.5 mm²
  • Signal suppression

    50 ms, 500 ms, 2 s or 4 s, selectable via DIP switches
  • Zero point correction

    Yes
  • Overload resistance

    Up to 100 hPa for the 10 hPa version; to 800 hPa for the 100 hPa version
  • Burst pressure

    150 hPa or 1000 hPa, depending on the main range
  • Security class

    IP54
  • Display

    Optional LCD display
  • Main areas of use

    Clean rooms, filter contamination control, ventilation and air conditioning systems

AVAILABLE MODELS

DOCUMENTS

  • Brochure: Pressure

    8.74 MB

    Download
  • Declaration of conformity: EU declaration of conformity

    165.07 KB

    Download
  • Ordering information: 402006

    113.26 KB

    Download
  • Brochure: Heating and Air Conditioning Industry

    6.55 MB

    Download
  • Datasheet: Multi-range pressure and differential pressure transmitter

    228.75 KB

    Download
  • Operating Instructions: Multi-range pressure and differential pressure transmitter

    468.93 KB

    Download