Fields of application

Danfoss iC7-HVACR ULH frequency converters are designed for HVACR systems where low harmonic distortion is important. They are suitable for controlling pumps, fans and compressors in commercial and industrial buildings.

 

Features:

  • Power range 22–160 kW

  • THDi <3 % at full load

  • Integrated STO safety function up to SIL3

  • Advanced Ethernet communication capabilities

  • IP20, IP21, IP54 and IP55 housing options

  • SPECIFICATIONS
  • AVAILABLE MODELS
  • DOCUMENTS

SPECIFICATIONS

  • Dedicated

    For controlling pumps, fans and compressors in HVACR systems where extremely low harmonic distortion levels are required.
  • Input voltage

    3 × 380-480 V AC, -15 % / +10 %
  • Power frequency

    45-65Hz
  • Power

    22-160kW
  • Rated output current

    43–302 A
  • Output frequency

    0-590Hz
  • Security class

    22–55 kW:
    IP21 or IP55

    75–160 kW:
    IP20, IP21 or IP54
  • Maximum overload

    110 % – for fans, pumps and compressors
    150 %
  • Harmonic distortion

    THDi <3 % at full load
    THDi <5 % at 50-90 % load
  • Functional safety

    STO – SIL3 / PL e
  • Programmable digital inputs and outputs

    DI – 4 + 2, 0/24 V DC, selectable PNP or NPN logic
    DO – 2, 0/24 V DC
  • Programmable analog inputs and outputs

    AI – 2
    0-10V or 0/4-20mA
    Support for Pt1000, Ni1000, KTY81, KTY82 and KTY84 sensors

    AO – 1
    0/4-20mA
  • Programmable relay outputs

    2 × NO/NC
    250V AC / 2A
  • Communication protocols

    Ethernet: Modbus TCP, EtherNet/IP, PROFINET RT, EtherCAT
    Serial communication: Modbus RTU