Models
IST7-60, IST7-80, IST7-100, IST7-120, IST7-160. IST7-200
Input — Voltage (VAC)
380/400/415 (138~485 LL)
Input — Frequency (Hz)
40~70
Input — Bypass Voltage (VAC)
+20% (optional -10% / -15% / -30%) / +15% (optional 10% / 20% / 25%)
Input — Power Factor
≥0.99
Entrance — THDI
<3 %
Input — Phases
3+N+PE
Output — Power (kVA)
IST7-60: 60
IST7-80: 80
IST7-100: 100
IST7-120: 120
IST7-160: 160
IST7-200: 200
Output — Power Factor
1
Output — Voltage (VAC)
LN: 220/230/240±1% LL: 380/400/415±1%
Output — Frequency (Hz)
50/60 ±0.1
Output — THD
3+N+PE
Output — Voltage stabilization
≤2 % under fully unbalanced load
Output — Waveform
Pure sine wave, THDv <1 % under linear load, THDv <3 % under non-linear load
Output — Efficiency
97%
Exit — Overload
≤130 % – long-term work
130–150 % – 5 minutes.
150–200 % – 1 sec
200–300 % – 100ms
300 % – immediate shutdown.
Battery voltage (VCC)
±168 ~±288 configurable
Battery Configurations Standard
External
Batteries - Max. charging current
IST7-60, IST7-80, IST7-100: 30
IST7-120, IST7-160. IST7-200: 60
Communication
RS485, MODBUS, free contact card (SNMP - optional)
Display
Touch screen + LED
Alarms
Low batteries, abnormal input, overload, jam/failure, etc.
Protection
Low charge, overload, short circuit, overheating, etc.
Noise
<65 (dB)
Temperature (°C)
0~40
Humidity
0 ~ 95 %
Dimensions (L×W×H) (mm)
IST7-60, IST7-80, IST7-100: 400×960×1200
IST7-120, IST7-160. IST7-200: 600×1000×1600
Weight (KG)
IST7-60: 145
IST7-80: 161
IST7-100, IST7-120: 171
IST7-160: 312
IST7-200: 320
Standards and certificates
CE (reference standards: safety IEC EN 62040-1; EMC IEC EN 62040-2; classification IEC EN 62040-3)