Fields of application
This flowmeter can be installed on cold and hot water pipes throughout the building (pure water manufacturing processes, equipment cleaning and cooling processes). The flowmeter can also be mounted inside equipment where there is a dense network of small-diameter pipes (semiconductor manufacturing equipment).
Features
Main unit type
FSZ08, Pipe diameter - 8A, 10A
FSZ15, Pipe diameter -15A, 20A
FSZ25, Pipe diameter - 25A, 32A
Configuration
Integrated transmitter and flow sensor
Mounting method
Clamp-on type
Measurement method
Transit time measurement method
Measuring fluid
Homogeneous fluids where ultrasonic signals can be transmitted
Measurement range
0 to ±5 m/s (Min. 0 to ±0.2 m/s)
Accuracy
Speed from 1 m/s to 5 m/s: ±2% of flow rate
Speed below 1 m/s: ±0.02 m/s
Straight pipe length required
Upstream 10D or more; downstream 5D or more (D: inside diameter of pipe)
Pipe material
Metals (stainless steel, steel, copper) Plastics (PVC, PP, PVDF)
Pipe thickness
1.2mm - 4.9mm
Response time
0.5 seconds
Temperature and humidity of fluid
-15 to +85°C (may vary depending on ambient temperature)
Analog output signal
4 to 20 mA DC : 1 point
Load resistance: 550 Ω max
Digital output
Outputs can be assigned to total normal and alarms as required
Transistor contact (open collector)
- Outputs: 2
- Normal: ON/OFF selection
- Contact rating: 27.5 V DC, 100 mA
- Output frequency: Max. 100 P/s (Pulse width 5, 10, 50, 100, 200 ms)
Connectivity
RS-485 (MODBUS)
Number of connectable modules: up to 31
Baud rates: 9600, 19200, 38400 bps
Parity: None/odd/even, selectable
Stop bit: 1 or 2 bits, selectable
Cable length: up to 1 km
Data: throughput, pipe temperature, forward total, error information, etc.
Display
4-digit 2-line LED display
Security class
IP65/lP67
Ambient temperature
-15 to +60°C
Ambient humidity
95% HR or less
Power supply/consumption
20 to 27.5 V DC, 2.5 W or less
Weight
FSZ08: 400 g FSZ15: 500 g FSZ25: 600 g
Product code | Diameter | Power supply | Additional functions | Version | Price |
---|---|---|---|---|---|
FSZ15YY2 | DN15 (1/2B) | 20–27,5 V AC | Without | Without | |
FSZ15YT2 | DN15 (1/2B) | 20–27,5 V AC | Pipe temperature measurement | Without | |
FSZ25YY2 | DN25 (1B) | 20–27,5 V AC | Without | Without | |
FSZ25YT2 | DN25 (1B) | 20–27,5 V AC | Pipe temperature measurement | Without | |
FSZ08YY2 | DN8 (1/4B) | 20–27,5 V AC | Without | Without | |
FSZ08YT2 | DN8 (1/4B) | 20–27,5 V AC | Pipe temperature measurement | Without |
Manual: Compact ultrasonic flow meter S-flow converter FSZ cable FLYF
6.3 MB
DownloadManual: Compact ultrasonic flowmeter S-flow FSZ sensor FLYF cable communication functions
1.58 MB
DownloadDatasheet: Integrated compact ultrasonic flow meter S-flow sensor FSZ cable FLYF
965.28 KB
DownloadBrochure: Ultrasonic flow meters for liquids, steam and gas
7.07 MB
DownloadBrochure: Compact ultrasonic flow meter S-flow FSZ
5.65 MB
DownloadBrochure: Measures for energy and the environment
4.01 MB
Download