BENNING UPS ENERTRONIC modular SE – modular UPS system 10–1000 kW

DC power supply, DC power systems

Fields of application

Protection of critical processes from network disruptions: IT and data centers, telecommunications, process automation, infrastructure (including energy and transport), oil, gas and petrochemical industries; marine version – for ships and offshore platforms.

 

Features:

  • Modules 10, 20 and 40 kW, up to 1000 kW in a system, hot swappable in less than 10 minutes.
  • No single point of failure, multi-master operation, N+1 self-configuration
  • Utility up to 96 %, and in SE mode up to 99 %
  • Classification VFI-SS-111, THDi up to 3 %, power factor not less than 0.99
  • Pay as you grow: power can be expanded or reduced with modules
  • Monitoring via MCU 3000 with 10″ touch screen
  • SPECIFICATIONS
  • AVAILABLE MODELS
  • DOCUMENTS

SPECIFICATIONS

  • Manufacturer

    BENNING
  • Series

    ENERTRONIC modular SE
  • Device type

    Modular UPS system (double conversion on-line UPS), classification VFI-SS-111 according to IEC / EN 62040-3
  • System power

    10–1000 kW (cos φ = 1.0), up to 25 modules in a system; systems can be connected in parallel
  • Module powers

    10 kW (1 phase), 20 kW (3 phases), 40 kW (3 phases)
  • Accessibility

    Up to "six nines" (99.9999 %); no single point of failure: critical circuits reserved in each module, multi-master operation, decentralized parallel architecture
  • Reservation

    Automatic module configuration N+1; black start
  • Utility

    Up to 96 % in double conversion mode; up to 99 % in Super Efficiency (SE) mode
  • Input quality

    THDi no more than 3 %; input power factor no less than 0.99 (adjustable); 3-level IGBT technology
  • Output quality

    Static tolerance ±1 %; frequency tolerance ±0.1 %; THDu at linear load no more than 1 %
  • Inverter overload

    150 % 60 s; 125 % 10 min; 110 % 30 min
  • Bypass overload

    1000 % 100 ms; 150 % at least 10 min; 125 % continuously
  • Power optimization

    Automatic TCO and availability optimization: Unnecessary modules go into sleep mode and remain ready to take over the load
  • Power density

    Up to 415 kW/m²; top ventilation (rear optional) and front service: cabinet can be placed against a wall or in a corner
  • Wardrobe area

    600 × 800 mm (width × depth)
  • Paint

    RAL 7035 / RAL 7021 (other colors on request)
  • Cable entry

    From below (from above on request)
  • Ventilation

    Reserved forced ventilation
  • Monitoring

    MCU 3000: 10″ touch screen in cabinet door or 19″ 1U unit (1.8″ screen, USB 2.0, Ethernet); web browser, TCP/IP, RS232
  • Additionally

    Can be expanded to hybrid UPS energy storage system; railway version ENERTRONIC modular SE RAIL (16.7 Hz / 50 / 60 Hz) on request