BENNING UPS ENERTRONIC modular SE – modular UPS system 10–1000 kW
DC power supply, DC power systems
Fields of application
Protection of critical processes from network disruptions: IT and data centers, telecommunications, process automation, infrastructure (including energy and transport), oil, gas and petrochemical industries; marine version – for ships and offshore platforms.
Features:
Modules 10, 20 and 40 kW, up to 1000 kW in a system, hot swappable in less than 10 minutes.
No single point of failure, multi-master operation, N+1 self-configuration
Utility up to 96 %, and in SE mode up to 99 %
Classification VFI-SS-111, THDi up to 3 %, power factor not less than 0.99
Pay as you grow: power can be expanded or reduced with modules
Monitoring via MCU 3000 with 10″ touch screen
SPECIFICATIONS
AVAILABLE MODELS
DOCUMENTS
SPECIFICATIONS
Manufacturer
BENNING
Series
ENERTRONIC modular SE
Device type
Modular UPS system (double conversion on-line UPS), classification VFI-SS-111 according to IEC / EN 62040-3
System power
10–1000 kW (cos φ = 1.0), up to 25 modules in a system; systems can be connected in parallel
Up to "six nines" (99.9999 %); no single point of failure: critical circuits reserved in each module, multi-master operation, decentralized parallel architecture
Reservation
Automatic module configuration N+1; black start
Utility
Up to 96 % in double conversion mode; up to 99 % in Super Efficiency (SE) mode
Input quality
THDi no more than 3 %; input power factor no less than 0.99 (adjustable); 3-level IGBT technology
Output quality
Static tolerance ±1 %; frequency tolerance ±0.1 %; THDu at linear load no more than 1 %
Inverter overload
150 % 60 s; 125 % 10 min; 110 % 30 min
Bypass overload
1000 % 100 ms; 150 % at least 10 min; 125 % continuously
Power optimization
Automatic TCO and availability optimization: Unnecessary modules go into sleep mode and remain ready to take over the load
Power density
Up to 415 kW/m²; top ventilation (rear optional) and front service: cabinet can be placed against a wall or in a corner
Wardrobe area
600 × 800 mm (width × depth)
Paint
RAL 7035 / RAL 7021 (other colors on request)
Cable entry
From below (from above on request)
Ventilation
Reserved forced ventilation
Monitoring
MCU 3000: 10″ touch screen in cabinet door or 19″ 1U unit (1.8″ screen, USB 2.0, Ethernet); web browser, TCP/IP, RS232
Additionally
Can be expanded to hybrid UPS energy storage system; railway version ENERTRONIC modular SE RAIL (16.7 Hz / 50 / 60 Hz) on request