BENNING UPS ENERTRONIC I – industrial uninterruptible power supply system (UPS)
DC power supply, DC power systems
Fields of application
Power supply of critical consumers that require voltage independent of network disturbances: petrochemical plants, oil refineries, power plants and substations, process computers, control centers, SCADA systems.
Features:
Highest UPS classification VFI-SS-111 according to IEC/EN 62040-3
Power from 10 to 500 kVA, three-phase or single-phase output
IGBT rectifier and inverter, power factor not less than 0.99, THDi up to 5 %
Electronic switching unit (EUE) and internal service bypass
Up to 8 units in parallel for redundancy or capacity expansion
Touch panel and 8000 event log
SPECIFICATIONS
AVAILABLE MODELS
DOCUMENTS
SPECIFICATIONS
Manufacturer
BENNING
Series
UPS ENERTRONIC I
Device type
Industrial double conversion uninterruptible power supply (UPS), single-phase and three-phase output
Classification
VFI-SS-111 according to IEC / EN 62040-3
Power limits
10–500 kVA (higher upon request)
Battery voltage limits
110, 220 or 384 V DC (external battery: lead, NiCd or lithium-ion)
Input
3/N 400 V ±10 % (others on request); 50 Hz ±10 % / 60 Hz ±10 %; power factor not less than 0.99; THDi not more than 5 %
Output parameters
Three-phase 380 / 400 / 415 V (3-3) or single-phase 220 / 230 / 240 V (3-1); static tolerance ±1 %; frequency tolerance ±0.1 %; THDu at linear load not more than 2 %
Inverter overload
200 % 1 s; 150 % 60 s; 125 % 10 min
Technology
IGBT rectifier and inverter; rectifier with power factor correction; optional thyristor rectifier (SCR)
Bypass
Electronic switchgear (EUE) with static bypass; internal service (manual) bypass; optional external manual bypass cabinet
Parallel work
Up to 8 ENERTRONIC I units in parallel (for backup or capacity increase) with active load sharing; Group-Connector
Control
Touch panel with energy flow and status graphics; event log for the last 8000 events; remote control functions
From 0 to +40 °C (power is reduced if exceeded); humidity 5–95 % without condensation; altitude up to 1000 m without power reduction; noise about 65 dBA
Ventilation
Reserved forced ventilation
Color and cable entry
RAL 7035 (others on request); cable entry from below (from above on request)