BENNING UPS ENERTRONIC I – industrial uninterruptible power supply system (UPS)

DC power supply, DC power systems

Fields of application

Power supply of critical consumers that require voltage independent of network disturbances: petrochemical plants, oil refineries, power plants and substations, process computers, control centers, SCADA systems.

 

Features:

  • Highest UPS classification VFI-SS-111 according to IEC/EN 62040-3
  • Power from 10 to 500 kVA, three-phase or single-phase output
  • IGBT rectifier and inverter, power factor not less than 0.99, THDi up to 5 %
  • Electronic switching unit (EUE) and internal service bypass
  • Up to 8 units in parallel for redundancy or capacity expansion
  • Touch panel and 8000 event log
  • SPECIFICATIONS
  • AVAILABLE MODELS
  • DOCUMENTS

SPECIFICATIONS

  • Manufacturer

    BENNING
  • Series

    UPS ENERTRONIC I
  • Device type

    Industrial double conversion uninterruptible power supply (UPS), single-phase and three-phase output
  • Classification

    VFI-SS-111 according to IEC / EN 62040-3
  • Power limits

    10–500 kVA (higher upon request)
  • Battery voltage limits

    110, 220 or 384 V DC (external battery: lead, NiCd or lithium-ion)
  • Input

    3/N 400 V ±10 % (others on request); 50 Hz ±10 % / 60 Hz ±10 %; power factor not less than 0.99; THDi not more than 5 %
  • Output parameters

    Three-phase 380 / 400 / 415 V (3-3) or single-phase 220 / 230 / 240 V (3-1); static tolerance ±1 %; frequency tolerance ±0.1 %; THDu at linear load not more than 2 %
  • Inverter overload

    200 % 1 s; 150 % 60 s; 125 % 10 min
  • Technology

    IGBT rectifier and inverter; rectifier with power factor correction; optional thyristor rectifier (SCR)
  • Bypass

    Electronic switchgear (EUE) with static bypass; internal service (manual) bypass; optional external manual bypass cabinet
  • Parallel work

    Up to 8 ENERTRONIC I units in parallel (for backup or capacity increase) with active load sharing; Group-Connector
  • Control

    Touch panel with energy flow and status graphics; event log for the last 8000 events; remote control functions
  • Transformers

    Output isolation transformer; input isolation transformer – optional (for 384V battery systems)
  • Security class

    IP20 (other on request)
  • Environment

    From 0 to +40 °C (power is reduced if exceeded); humidity 5–95 % without condensation; altitude up to 1000 m without power reduction; noise about 65 dBA
  • Ventilation

    Reserved forced ventilation
  • Color and cable entry

    RAL 7035 (others on request); cable entry from below (from above on request)
  • Standards

    IEC/EN 62040-1, IEC/EN 62040-2, IEC/EN 62040-3, IEC/EN 62477-1
  • Additionally

    Optional high short-circuit current up to 4 × Inom; optional temperature-compensated charging characteristic