en
  • lt
  • en

Piller APOTRANS AT 125–1600 A – static transfer switch (STS)

Static Transfer Switches, UPS

Fields of application

PILLER APOTRANS AT 125–1600 A – high-current static transfer switches (STS) that automatically switch critical loads to a backup source when the main source deviates from the norm or disappears. Designed for data centers, industry and other critical infrastructure where a backup source is required up to the load, in new and existing power systems.

 

Features:

  • Current range from 125 to 1600 A
  • Fuse-free: large thyristors with high short-circuit resistance simplify protection coordination
  • Switching typically within 3 ms per phase; safely switches even 180° out-of-sync sources
  • Redundant controllers, triple redundant power supplies, redundant fans
  • Continuous thyristor control and adaptive short-circuit detection on the load side
  • Inrush current control protects the transformer during switching
  • 3 or 4 pole versions; cabinet or open frame for integration into PDUs and distribution boards
  • Programmable switching windows, voltage and frequency tolerances; interface with UPS systems
  • SPECIFICATIONS
  • AVAILABLE MODELS
  • DOCUMENTS

SPECIFICATIONS

  • Manufacturer

    PILLAR
  • Series

    APOTRANS AT
  • Device type

    Thyristor static switch (STS)
  • Rated current

    125–1600 A
  • Piles

    3 or 4 poles (4 poles: neutral conductor switching in TN-S systems)
  • Construction

    Fuseless
  • Switching time

    Typically 3 ms per phase, phase selective switching
  • Unsynchronized sources

    Safe switching with 180° phase shift
  • Reservation

    Redundant controllers, triple power supplies, duplicated fans
  • Thyristor control

    Continuous; short circuit and open circuit detection with signal; active and inactive thyristors checked during each cycle
  • Short circuit protection

    Adaptive detection; the switch does not turn on the source in the event of a short circuit on the output
  • Ignition current control

    Limits transformer inrush currents during manual and automatic switching
  • Programmable parameters

    Switching windows, input voltage tolerance, input frequency tolerance
  • Interface with UPS

    External signals adapt operation to UPS status
  • Housings

    Cabinet or open frame
  • Cable entry

    From above, below or both sides
  • Access

    Full service from the front
  • AT 1600 A

    Four-pole cabinet with isolating and bypass switches and electromagnetic bypass switch interlock
  • Dimensions and weight

    According to the specific model (specified by the manufacturer)
  • Applications

    Data centers, industry, critical infrastructure
  • Additional equipment available

    Open frame version for integration into distribution panels and switchboards

    3 or 4 pole version according to system requirements

    Cabinet version with isolation and bypass switches

    Integration into isolated, distributed or "system + system" reservation schemes

AVAILABLE MODELS