Home > Products > Frequency converters > VACON 20
- SPECIFICATIONS
-
AVAILABLE MODELS
- DOCUMENTS
SPECIFICATIONS
Documentation
Selection guide: VACON 20Dedicated
for the control of pumps, fans and compressors
Housing
MI1 ÷ MI5
Power
0.25 ÷ 18.5kW
Input voltage
208 ÷ 240 V; 380 ÷ 480 V
Current
1.3 ÷ 38 A
Input
AI1: 1 x 0 ÷ 10VAC, AI2: 1 x 0 ÷ 10VDC/0/4 ÷ 20mA, DI1 -DI6: 0-+30V Ri = 12 kΩ
Output
AO: 1 x 0 ÷ 10V / 0(4) ÷ 20mA, DO: open collector, max. overload: 48 V/50 mA, ModBus RTU RS485, RO: 2 x relays
Output frequency
0 ÷ 320Hz, resolution: 0.01Hz
Overload
Inom x 1.5 max. 1min/10min
Max. launch current
2 x Inom, 2 sec. every 20 sec.
Control
Vector, potentiometer, PI controller, "sleep" mode (SW)
Ambient temperature
-10 ÷ 50°C, 95% RH
Security class
IP20/21
Electromagnetic compatibility
RFI filter, C2, EN61800-3
Communications
ModBus RS485 (standart)
Certificates
EN61800, C-Tick, Gost R, CB, CE, UL, cUL, KC